Frida TD 24kV VLF
High voltage VLF tester and integrated tan delta diagnostics device Up to 26.1 kVrms, 34 kV peak
Call us on 1300 024 473 for fantastic long term hire rates.
Description
The new cable condition evaluation generation
- Cable testing and dissipation factor diagnostics in one device
- Easy and quick test setup
- Automatic testing and diagnostic sequences
- Compact dimensions and lightweight
The portable BAUR frida and frida TD devices are used
- for testing medium-voltage cables and electrical equipment (generators, transformers and switchgear)
- for cable sheath testing
- for cable diagnostics (frida TD):
- Dissipation factor measurement and Monitored Withstand Test with tan δ
- Partial discharge measurement*
- Full Monitored Withstand Test with tan δ and partial discharge measurement*
The VLF testing makes it possible to locate insulation faults in plastic- and paper-insulated mass-impregnated cables in the shortest of testing times without impairing the quality of the surrounding insulating material. The dissipation factor diagnostics with 0.1 Hz VLF truesinus® provides differentiated information on the ageing condition of paper-insulated mass-impregnated and PE/XLPE cables. In the case of PE/XLPE cables, the dissipation factor measurement is capable of differentiating between new, slightly or severely “water tree”-damaged cables. This makes it possible to prioritise the need to replace cables. The Monitored Withstand Test with tan delta combines the cable testing and dissipation factor measurement, allowing an accurate and comprehensive assessment of the cable condition. In addition, there is minimum load on the cable due to the optimised test duration.
Output voltage
Frequency range: 0.01 – 0.1 Hz
VLF truesinus®: 1 – 42.5 kVrms (60kVpeak)
VLF square wave voltage 1 – 60 k
VDC voltage: ±1 – 60 kV
Resolution: 0.1 kV
Accuracy: 1 %
Load range (VLF testing): 1 nF – 10 µF
Output current
Measurement range: 0 – 14 mA
Resolution: 1 µA
Accuracy: 1%
Max. capacitive load:
- 0.5 μF at 0.1 Hz
- 24 kVrms / 34 kVpeak(=2 km)*
- 1 μF at 0.05 Hz,
- 24 kVrms / 34 kVpeak(=4.2 km)*
- 8 μF at 0.01 Hz,
- 18 kVrms / 25 kVpeak(=33 km)*
- *max. cable length at a cable capacity of 0.24 µF/km
Dissipation factor measurement (viola TD)
VLF truesinus®: 1 – 24 kVrms
Load range: 10 nF – 10 µF
Resolution: 1 x 10-6
Accuracy: 1 x 10-4
Measurement range: 1 x 10-4 – 21000 x 10-3
tan d measuring frequency: 0.1 Hz
General
Input voltage: 100 – 260 V, 50/60 Hz
Power consumption: Max. 1 400 VA
Reverse voltage protection: 13 kV
Degree of protection: IP 54
Data interface: USB 2.0
Dimensions (W x H x D): 438 x 456 x 220 mm
Weight (include HV test lead): Approx. 22 kg
Ambient temperature (operational): -10°C to +50°C
Storage temperature: -20°C to +60°C
Safety and EMC:
- CE-compliant in accordance with Low Voltage Directive (2006/95/EC)
- EMC Directive (2004/108/EC)
- EN 60068-2-ff Environmental testing
Resources & Downloads
Hiring with Brandis Hire is easy
Find your Gear (and rates)
Browse our range to find the equipment you need. Select your hire dates and get instant pricing
Submit a Booking Request
Provide your details and submit your hire request online in minutes. We will be in touch to confirm everything
Pick up or we deliver
Your gear will be prepared and ready for you to collect, or let us take care of shipping direct to you
Brandis Hire can help!
We’re here to help make hiring technical equipment easy!
No lock-in hire periods
4 hours FREE technical support
Delivery and pickup options available
We care about our customers
Download full price list
By entering your email address, you agree to sign up to occasional marketing communications from Brandis Hire.
"*" indicates required fields
By entering your email address, you agree to sign up to occasional marketing communications from Brandis Hire.