0-60 kV VLF Tester for HV Cable Testing
The most advanced HV test system with the highest output power of any unit available.

Available: 1

Categories: , ,

Need assistance? Give us a call or email, we will be happy to help.

All equipment is supplied with a calibration certificate ("if Applicable"), tested & checked before we dispatch it and transported in a heavy duty transport case.


HVA60 VLF User Manual

The most advanced HV test system available, with the highest output power of any unit available.
Lightest, most compact instrument of its type available with control cabinet and HV generator all contained in one box.
Offering variable frequency VLF output for testing of HV Cables and Switchgear, the operator can also select dual polarity DC and cable jacket or sheath testing output modes.
The applied test voltage, current, capacitance, resistance and time are displayed and recorded.
Easily programmable allowing test sequences in either automatic or manual mode.
Capable of testing  approx 3000m of cable at 0.1Hz and 60kV peak. At 0.02Hz, approx. 15,000m of cable can be tested.

If cable burning (fault conditioning) mode is activated, the fault resistance can be conditioned to allow easier and less stressful fault location.

Available Modes: VLF (0.1Hz), DC (±), Cable Fault Conditioning (Burning), and Sheath/Jacket Testing
Fully Automatic or manual cable test sequences
Real-time Display of actual output waveform
Easy to use, ergonomic, menu guided, large backlit user interface

Standard Accessories Transport Case, Mains cable, HV output cable earth cable, RS232 cable Operating manual
Power Supply 100-240VAC, 50/60Hz
Output Voltage  Sinusoidal: 0 — 60kV peak
DC: ±0 — 60kV
Square wave: 0 — 60kV peak
Output Current 0 —50mA. Resolution 1µA
Output Frequency 0.02 – 0.1 Hz. In steps of 0.01 Hz
Output Modes AC (VLF) Symmetrical and load independent over full range
DC positive and negative polarity
Burn / Fault condition or Fault trip mode
Jacket / Sheath testing
Output Load 1.0µF at 0.1Hz at 43kV rms (approx 3km of cable)
2.0µF at 0.05Hz at 43kV rms (approx 6km of cable)
5.0µF at 0.02Hz at 43kV rms (approx 15km of cable)
50µF at reduced voltage and/or frequency
Metering Output voltage and current (true RMS and Peak) Capacitance, Resistance, Time, Flashover voltage
Dimensions (instrument) 450 L x 350 W x 510 H mm
Weight 59.8kg