$215.00 / day

8-14 days : $193.50 / day
15-28 days : $172.00 / day
29-90 days : $150.50 / day
91-180 days : $129.00 / day
181 days+ : $107.50 / day
365 days+ : by agreement. Please contact us.

Accessory for the CPC 100, to measure line impedances and k-factors on overhead lines and power cables, Ground impedances on large earthing systems, as well as touch and step voltages.

Available: 1

Categories: , , ,

Need assistance? Give us a call or email, we will be happy to help.

All equipment is supplied with a calibration certificate ("if Applicable"), tested & checked before we dispatch it and transported in a heavy duty transport case.


CP CU1 Reference Manual

The CPC 100 + CP CU1 measure line impedances and k-factors on overhead lines and power cables. Ground impedances can also be determined on large systems with the CP CU1, as well as touch and step voltages.

Mains frequency malfunctions do not influence the measurements, as the CPC 100 + CP CU1 use variable output frequencies for measurements. This enables extremely precise and reproducible measurement results.

To increase safety for the test engineer, the CP GB1 grounding unit is supplied with the CP CU1. This can divert currents of up to 30 kA if its voltage limit value is exceeded.

Key features
  • Measurement is not affected by mains frequency interference – extremely precise measurement results are obtained
  • Compliance with the strictest safety standards for overhead lines and cables connections – diverting currents up to 30 kA
  • Easy to handle – heaviest component: 29 kg
  • Automatic logging: Results are recorded automatically by the software
  • Line impedances and k-factors of overhead lines or high-voltage cables
  • Ground impedances of large systems
  • Step and touch voltages
  • Mutual coupling of parallel overhead lines
  • Coupling of power lines into signal cables
Standard Accessories Refer accessories list in users manual
Power Supply Directly powered from the CPC100 instrument
Current Output Ranges 10A, 20A, 50A, 100A RMS
Output Power 5000 VA (45…70 Hz), cosφ < 1.0 for 8 s at 230 V AC
mains voltage
Frequency Range 15…400 Hz (15…45 Hz with reduced voltage)
Operating Temperature/Humidity Range -10 to 55°C and 5 to 95%RH (no condensation)
Dimensions (W x H x D) (CU1 Instrument Only) 450 × 220 × 220 mm
Dimensions (W x H x D) (GB1 Grounding Box Only) 200 × 190 mm
Weight (CU1 Instrument) 28.5kg
Weight (GB1 Instrument) 4.2kg

Additional information

Weight 54 kg
Dimensions 70 x 46 x 41 cm


There are no reviews yet.